Data Point Name
|
Access
|
Value Type
|
Point Source
|
Description
|
|
Amps A |
Read Only |
Analog |
Generator Controller (or meter if not present) |
Amps on leg A measured at the output of the generator. |
|
Amps B |
Read Only |
Analog |
Generator Controller (or meter if not present) |
Amps on leg B measured at the output of the generator. |
|
Amps C |
Read Only |
Analog |
Generator Controller (or meter if not present) |
Amps on leg C measured at the output of the generator. |
|
Battery Charge Alarm |
Read Only |
Digital |
Generator Controller |
Engine battery charger has gone into alarm. This is a warning alarm and could prevent the engine from running. |
|
Battery Voltage |
Read Only |
Analog |
Generator Controller (blank if not present) |
Battery voltage in volts of the engine batteries. |
|
Common Alarm |
Read Only |
Digital |
Generator Controller (hard-wired if not present) |
True if any alarm (warning or shutdown) is present on the engine. If true, engine may not run when called up for dispatch. |
|
Coolant Temp |
Read Only |
Analog |
Generator Controller (blank if not present) |
Engine coolant temperature of the engine in degrees F. |
|
Emergency Stop |
Read Only |
Digital |
Generator Controller |
The Emergency stop button has been hit at the Generator. This is a shutdown alarm, the Generator will not run until the button is released and alarm is cleared onsite. |
|
Frequency |
Read Only |
Analog |
Generator Controller (or meter if not present) |
Voltage frequency measured at the output of the generator. |
|
Fuel Level |
Read Only |
Analog |
Generator Controller (blank if not present) |
For diesel engines, fuel level remaining of diesel belly tank. |
|
High Battery Volts |
Read Only |
Digital |
Generator Controller |
High battery voltage is detected on the engine batteries. Generator will run but further onsite investigation is needed. |
|
High Engine Temp |
Read Only |
Digital |
Generator Controller |
Engine coolant temp has gone above the critical level. This is a shutdown alarm, generator will not run until this is addressed onsite. |
|
kVAR |
Read Only |
Analog |
Generator Controller (or meter if not present) |
Reactive power reading measured at the output of the generator. |
|
kW |
Read Only |
Analog |
Generator Controller (or meter if not present) |
Real power reading measured at the output of the generator. |
|
kWh |
Read Only |
Analog |
Generator Controller (or meter if not present) |
Total real power consumption measured at the output of the generator. |
|
Low Battery Volts |
Read Only |
Digital |
Generator Controller |
Low battery voltage is detected on the engine batteries. Generator will run but further onsite investigation is needed. |
|
Low Coolant Level |
Read Only |
Digital |
Generator Controller |
Engine coolant level has gone below the critical level. This is a shutdown alarm, generator will not run until this is addressed onsite. |
|
Low Coolant Temp |
Read Only |
Digital |
Generator Controller |
Engine coolant temp has gone below the critical level. This is a shutdown alarm, generator will not run until this is addressed onsite. |
|
Not in Auto |
Read Only |
Digital |
Generator Controller (hard-wired if not present) |
True when engine is taken OUT of Auto and put into either the Manual or Off position. If true, engine will not run as expected when called upon for dispatch. |
|
Oil Pressure |
Read Only |
Analog |
Generator Controller (blank if not present) |
Oil pressure of engine in PSI. |
|
Oil Pressure Low |
Read Only |
Digital |
Generator Controller |
Engine oil pressure has gone below the critical low level. This is a shutdown alarm, generator will not run until this is addressed. |
|
Overcrank |
Read Only |
Digital |
Generator Controller |
Engine is attempting to start but is not able. This is a shutdown alarm, generator will not run until this is addressed. |
|
Overspeed |
Read Only |
Digital |
Generator Controller |
Engine speed has gone above expected operating parameters. This is a shutdown alarm, generator will not run until this is addressed. |
|
Power Factor |
Read Only |
Analog |
Generator Controller (or meter if not present) |
Power factor measured at the output of the generator. |
|
Pre High Engine Temp |
Read Only |
Digital |
Generator Controller |
Engine coolant temp has gone above the warning level. This is a warning alarm, generator will run but further site investigation is necessary. |
|
Pre Low Oil Pressure |
Read Only |
Digital |
Generator Controller |
Low engine oil pressure is detected. Generator will run but further onsite investgation is needed. |
|
Running |
Read Only |
Digital |
Generator Controller (hard-wired if not present) |
True when engine is running. |
|
Shutdown Alarm |
Read Only |
Digital |
Generator Controller |
Any shutdown alarm is present on the generator. The engine will not run until addressed or cleared. |
|
Supplying Load |
Read Only |
Digital |
Generator Controller (or meter if not present) |
Generator is providing standby power to the site. |
|
Start |
Read/Write |
Digital |
Generator Controller (hard-wired if not present) |
Remote start of generator. |
|
Volts AB |
Read Only |
Analog |
Generator Controller (or meter if not present) |
A to B line-to-line voltage reading at the output of the generator. |
|
Volts BC |
Read Only |
Analog |
Generator Controller (or meter if not present) |
B to C line-to-line voltage reading at the output of the generator. |
|
Volts CA |
Read Only |
Analog |
Generator Controller (or meter if not present) |
C to A line-to-line voltage reading at the output of the generator. |
|
Warning Alarm |
Read Only |
Digital |
Generator Controller |
Any warning alarm is present on the generator. The generator will run but further onsite investigation needs to be done. |